ChipFind - Datasheet

Part Number AP-B10

Download:  PDF   ZIP
Electrical data
Primary Nominal Current
Analogue Output Signal
Type
I
PN
(A.t.RMS)
V
OUT
(V)
10,25,50
0-5V or 0-10V
AP 50 B10
50,75,100
0-5V or 0-10V
AP 100 B10
100,150,200
0-5V or 0-10V
AP 200 B10
200,300,400
0-5V or 0-10V
AP 400 B10
R
L
Load resistance
10
k
V
C
Supply voltage
+24 ±5% V DC
V
d
R.m.s. voltage for AC isolation test,
50/60Hz, 1 mn
5
kV
Limitation voltage output
18
V
Accuracy-Dynamic performance data
X
Accuracy @
I
PN
,
T
A
= 25°C (without offset)
< ±1
% of
I
PN

L
Linearity (0 .. ±
I
PN
)
< ±0.5 % of
I
PN
V
OE
Electrical offset voltage,
T
A
= 25°C
< ±0.5 % of
I
PN
V
OT
Thermal drift of
V
OE
±1
mV/K
TC

G
Thermal drift of the gain (% of reading)
±0.1
%/K
t
r
Response time @ 90% of
I
P
< 500
ms
f
Frequency bandwidth (-3 dB)
10 .. 6000
Hz
General data
T
A
Ambient operating temperature
-20 .. +60
°C
T
S
Ambient storage temperature
-20 .. +85
°C
m
Mass
90
g
Protection type
IP20
Reliable isolation according to EN50178, EN61010
300
V AC
Creepage distance
>
5.5
mm
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
Notes :
Installation and maintenance should be done with power supply disconnected.
AC Current transducer AP-B10
Split core transducer for the electronic measurement AC waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Switch selectable ranges
and RMS 0-5V and 0-10V switch selectable voltage output.
I
PN
= 10 .. 400 A
030708/0
Features
·
RMS output
·
Split core type
·
5V & 10V switch selectable voltage
output.
·
DIN mounting & Panel mounting
·
Eliminates insertion loss
·
Switch selectable ranges
Advantages
·
Large aperture for cable up to Ø18mm
·
High isolation between primary and
secondary circuits
·
Easy to mount
Applications
·
Automation systems
Analog current reading for remote
monitoring (e.g. motor) and software
alarms.
·
Panelmeters
Simple connection displays power
consumption.
LEM Components
www.lem.com
Preliminary
Dimensions AP(R)-B10
(unit : mm, 1mm = 0.0394 inch)
Mechanical characteristics
·
General tolerance
±1 mm
·
Primary aperture
18.5 mm
·
Panel mounting
2 holes
4.0 mm
·
Distance between holes
40.0 mm
For panel mounting, replace M4 screws by new one (not supplied) with appropriate length to panel´s thickness.
Connections
·
Wires up to 2 mm
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
2 (out)1 (+)
3 (-)
O utput
R a n g e S w itc h
0-5, 10V Selec table
A P /A P R
C o n n e c to r
F ront
O utput S w itc h
G N D
O U T P U T
+2 4 V D C
R
L